数据中心固定分隔配电柜抗振性能分析

Analysis of Anti-Vibration Performance of Fixed Partition Distribution Cabinets in IDC

  • 摘要: 数据中心内的固定分隔配电柜用于数据中心内部的电能分配。柜体在运输过程中,受到行车调运和车辆载运等多种加速度作用,因此在保证其功能能实现的前提下,需要确保柜体具备较高抗振性能。该文以配电柜柜体为研究对象,首先基于MIL-STD-810F环境可靠性试验标准,应用CAD、SolidWorks建立实体模型;然后使用 SolidWorks Simulation部件对其进行振动分析,得到RMS和PSD两大结果数据,通过RMS结果得出最大应力值出现在托盘左右两侧,且大于材料屈服强度,通过PSD结果得出在13.62 Hz时柜体振动达到最大;最后在确保柜体抗振性能满足要求的前提下提出相关注意事项。

     

    Abstract: The fixed partition power distribution cabinet in an IDC is used for internal power distribution. During transportation, the cabinet is subjected to various acceleration loads caused by crane handling and vehicle transport. Therefore, on the premise of ensuring its functional performance, it is necessary to guarantee that the cabinet possesses adequate anti-vibration capability. This paper takes the power distribution cabinet as the research object. First, based on the MIL-STD-810F environmental reliability test standard, a three-dimensional solid model is established using CAD and SolidWorks. Then, vibration analysis is carried out using the SolidWorks Simulation module, and two key results RMS and PSD are obtained. The RMS results indicate that the maximum stress occurs on both sides of the tray and exceeds the material yield strength. The PSD results show that the cabinet vibration reaches its maximum at 13.62 Hz. Finally, under the premise that the cabinet's anti-vibration performance meets the required standards, relevant precautions and recommendations are proposed.

     

/

返回文章
返回